DGP2-641R LCD Keypad Module 21n
and will either beep as long as the Access Alarm is occurring or
follow the Beep Timer in section
[012]
. The sound of the Door Left
Open Alarm resembles the rapid beep generated during the last
ten seconds of the Exit Delay. When the door is closed during an
Access Alarm, the Door Left Open Restore event can be logged in
the Event Buffer.
Option [5] OFF = The Door Left Open Alarm is silent
Option [5] ON = The Door Left Open Alarm is audible (default)
If option [5] is enabled:
Option [6] OFF = Beep as long as the Door Left Open Alarm is
occurring (default)
Option [6] ON = Door Left Open Alarm follows Beep Timer
(section [012])
5.3.6 Beep Timer For Door Left Open Alarm
S
ECTION [012]
This beep timer determines the amount of time the Door Left
Open Alarm will beep. Once the Door Left Open Interval (see
section 5.3.2 on page 19) has expired, the Door Left Open
Alarm (see section 5.3.5 on page 20) will be triggered. Enter
any value between 001 and 255 to determine the number of
seconds the Access Alarm will beep. Default = 5 seconds.
5.4 Door Forced Open Options
The Door Forced Open Options allow you to program how the system
will react when an Access Control door is opened without a “Request
for Exit” or “Access Granted” signal.