Digiplex DGP2-641R Manuel d'installation Page 1

Naviguer en ligne ou télécharger Manuel d'installation pour Systèmes de contrôle d'accès de sécurité Digiplex DGP2-641R. Digiplex DGP2-641R Installation manual Manuel d'utilisatio

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer

Résumé du contenu

Page 1 - Built-in Reader (V2.0)

Access Control LCD Keypad Module with Built-in Reader (V2.0)DGP2-641RReference and Installation Manual DGP-641DGP2641R_ei00.fm Page -3 Thursday, Jul

Page 2

6 Reference & Installation ManualFigure 2: Typical Access Control InstallationFigure 3: Access Control Overview1 = Request for Exit (REX) device (

Page 3 - TABLE OF CONTENTS

DGP2-641R LCD Keypad Module 7nFigure 4: Access Control ConnectionsDGP2-641R DGP2-641RFused external power supply (recommended)Door LockIN4007DiodeDGP2

Page 4

8 Reference & Installation Manual3.0 PROGRAMMINGProgramming the DGP2-641R keypad module is simple. Enter Module Programming Mode, enter the desir

Page 5 - 1.0 INTRODUCTION

DGP2-641R LCD Keypad Module 9n3.2 Programming MethodsThe following methods can be used when programming the keypad:3.2.1 Feature Select ProgrammingSom

Page 6 - 1.1 Specifications

10 Reference & Installation Manual4.0 SYSTEM OPTIONS4.1 Partition AssignmentSECTION [001]: OPTIONS [1] TO [8]Keypads in the system can be assigned

Page 7 - 2.0 INSTALLATION

DGP2-641R LCD Keypad Module 11n4.4 Display Entry Delay TimerSECTION [003]: OPTION [3]The Entry Delay Timer will be programmed to provide the user time

Page 8 - 2.2 Connecting Keypad Zones

12 Reference & Installation ManualFigure 5: LCD Screen4.6 Confidential Mode TimerSECTION [007]Section [007] determines the amount of time without

Page 9

DGP2-641R LCD Keypad Module 13n4.9 Beep on Exit DelaySECTION [004]: OPTION [2]The keypad can beep once every second during the Exit Delay Timer. Durin

Page 10

14 Reference & Installation ManualOption [2] OFF= Beep disabled: Communicator TroublesOption [2] ON = Beep enabled: Communicator TroublesOption [3

Page 11 - Z1 terminal

DGP2-641R LCD Keypad Module 15nexternal power supply may correct the situation.1. From Normal Mode press and hold the [0] key.2. Enter the [INSTALLER

Page 12 - 3.0 PROGRAMMING

DGP2641R_ei00.fm Page -2 Thursday, July 22, 2004 4:16 PM

Page 13 - 3.3 Module Broadcast

16 Reference & Installation Manual5.2 Door Lock OptionsThe Door Lock Options allow you to program the door lock to suit its environment or securit

Page 14 - 4.0 SYSTEM OPTIONS

DGP2-641R LCD Keypad Module 17n5.2.4 Relock DoorSECTION [006]: OPTION [6]The locking device will remain unlatched during the Door Unlocked Period (see

Page 15 - 4.5 Confidential Mode

18 Reference & Installation ManualFor example, program:• Interval A: Start time 07:00, End time 16:00, Days M, T, W, T, & F• Interval B: Start

Page 16 - 4.8 Muting

DGP2-641R LCD Keypad Module 19n5.3.1 Door Left Open Access AlarmSECTION [006]: OPTION [2]When an Access Control door is opened after an Access Granted

Page 17 - 4.11 Beep on Trouble

20 Reference & Installation Manualreader to beep a certain time before the end of the Door Left Open Interval to alert users that the Access Contr

Page 18 - 4.14 Combus Voltmeter

DGP2-641R LCD Keypad Module 21nand will either beep as long as the Access Alarm is occurring or follow the Beep Timer in section [012]. The sound of t

Page 19 - 5.0 ACCESS CONTROL OPTIONS

22 Reference & Installation Manual5.4.1 Door Forced Open Access AlarmSECTION [006]: OPTION [3]If an Access Control door is opened without an Acces

Page 20 - 5.2 Door Lock Options

DGP2-641R LCD Keypad Module 23n5.4.3 Beep Timer For Door Forced Open AlarmSECTION [013]This Beep Timer determines the amount of time the Door Forced O

Page 21 - ECTION [017]

24 Reference & Installation Manual6.0 MESSAGE PROGRAMMINGSECTIONS [101] TO [396]Each section from [101] to [396] contains one message with a maxim

Page 22 - 5.3 Door Left Open Options

DGP2-641R LCD Keypad Module 25nThe DGP-NE96 control panel has up to 8 partitions, 96 zones and up to 999 user codes. This LCD keypad module only allow

Page 23 - ECTION [004]: OPTION [3]

TABLE OF CONTENTS1.0 INTRODUCTION ...11.1 Specifications ...

Page 24 - ECTION [011]

26 Reference & Installation ManualTable 2: Special Characters CatalogDGP2641R_ei00.fm Page 26 Thursday, July 22, 2004 4:16 PM

Page 25 - 5.4 Door Forced Open Options

DGP2-641R LCD Keypad Module 27n7.0 PROGRAMMING SECTIONSU = Default settingSECTION [001]: Keypad Partition AssignmentOption OFF ON [1] Parti

Page 26 - ECTION [006]: OPTION [3]

28 Reference & Installation ManualU = Default settingSECTION [003]: General Options 1Option OFF ON [1] Display code entry U Disabled N

Page 27 - 5.5 PIN Entry ON Keypad

DGP2-641R LCD Keypad Module 29nU = Default setting* This option cannot be turned ON and will always remain OFF.SECTION [005]: Beep on TroubleOption OF

Page 28 - 6.0 MESSAGE PROGRAMMING

30 Reference & Installation ManualSection [510]: Download from Memory Key (PMC-3) to DGP2-641R.Section [520]: Upload from DGP2-641R to Memory Key

Page 29

DGP2-641R LCD Keypad Module 31n8.0 GLOSSARYAccess Alarm: An audible or silent warning generated by the keypad to indicate that a protected door has no

Page 30

32 Reference & Installation ManualForced Door: If a protected door was opened without an “Access Granted” or “Request for Exit” signal, a silent o

Page 31 - 7.0 PROGRAMMING SECTIONS

DGP2-641R LCD Keypad Module 33nWarrantyParadox Security Systems Ltd. (“Seller”) warrants its products to be free from defects in materials and workman

Page 32

34 Reference & Installation ManualNOTESDGP2641R_ei00.fm Page 34 Thursday, July 22, 2004 4:16 PM

Page 33

DGP2641R_ei00.fm Page 35 Thursday, July 22, 2004 4:16 PM

Page 34

5.0 ACCESS CONTROL OPTIONS... 155.1 Assigning Doors To Partitions ... 155.2 Door

Page 35 - 8.0 GLOSSARY

Printed in Canada - 07/2004 DGP2641R-EI00DGP2641R_ei00.fm Page 36 Thursday, July 22, 2004 4:16 PM

Page 36

DGP2-641R LCD Keypad Module 1n1.0 INTRODUCTIONThe Digiplex™ Series Security Systems (DGP-848/DGP-NE96) are advanced technology security systems that w

Page 37

2 Reference & Installation Manual1.1 SpecificationsPower input: 9 to 16 VDC, 100mA maximumPGM current limit: 50 mANumber of inputs: 2Power indicat

Page 38

DGP2-641R LCD Keypad Module 3n2.0 INSTALLATIONThe DGP2-641R is connected to the control panel's combus in a star and/or daisy chain configuration

Page 39

4 Reference & Installation Manual2.1 Mounting the DGP2-641R on MetalAlthough metal may decrease the read range of it’s built-in reader, the DGP2-6

Page 40

DGP2-641R LCD Keypad Module 5nFigure 1: Connecting the Keypad and Keypad ZoneTo Digiplex series control panelCombusDGP2-641R* The keypad zone follows

Commentaires sur ces manuels

Pas de commentaire